operating ball valves and V-port valves.
Procedure for Single Acting Actuator
(including the model with manual operator “HW”)
1. Supply compressed air to the inlet port to
the valve open and check fully open position
of the valve.
2. If the position is not correct, exhaust the
compressed air letting the valve to close the
valve. Then perform the following steps 3
and 4.
3. Loosen hexagon nut for locking open
side stopper bolt, turn the stopper bolt
in respective direction by using hexagon
bar wrench. Clockwise turning of the bolt
reduces travel angle of the actuator, and
counterclockwise turning widen the range of
the travel angle.
4. After ensuring correct position of the valve
by supplying compressed air to the actuator,
tighten the locking nut of the stopper bolt.